Fibre Converter
ODW-710-F2 Series

The ODW-710-F2 has been designed to allow the use of fibre optic cables on Profibus DP networks. The design allows the use of a range of Westermo verified SFP (Small Form Pluggable) transceivers which can provide solutions with, for example, only a single fibre or distances up to 120 km. Both multidrop networks and redundant rings can be formed using a mixture of transceiver types.

Category:

The ODW-710-F2 has been designed to allow the use of fibre optic cables on Profibus DP networks. The design allows the use of a range of Westermo verified SFP (Small Form Pluggable) transceivers which can provide solutions with, for example, only a single fibre or distances up to 120 km. Both multidrop networks and redundant rings can be formed using a mixture of transceiver types.

This unit has been designed for industrial use where the requirement is for a long and reliable service life in a harsh environment. To ensure this reliable operation we manufacture using the highest quality components.

The ODW-710 can be used on all Profibus DP networks to extend the operational network size beyond the normal constraints of the copper cable. All the data rates defined in EN50170 are supported.

Large ring networks can be created to provide network resilience to guarantee system functionality even if a cable is damaged. The ring recovery time ensures that the network devices are not aware of the failure. The fault contact provides a method to communicate network failures.

• Product Description
Status Active
Article number 3651-0712
Ports 1 x Detachable screw terminal, Status
1 x PROFIBUS DP (RS-485)
1 x LC Duplex or LC Simplex, FX (Fibre)
Description Point-to-Point Fibre Converter, PROFIBUS
• Reliability prediction
Service life, operating 10 years
• EMC (Electromagnetic Compatibility)
EN 61000-6-1 Immunity residential environments
EN 61000-6-2 Immunity industrial environments
EN 61000-6-3 Emission residential environments
EN 61000-6-4 Emission industrial environments
EN 55022 Emission IT equipment, class A
EN 55024 Immunity IT equipment
FCC part 15 Class A
EN 50121-4 Railway signalling and telecommunications apparatus
IEC 62236-4 Railway signalling and telecommunications apparatus
• EMC Specification
EN 61000-4-2, ESD Enclosure contact, ± 6 kV
Enclosure air, ± 8 kV
IEC 61000-4-3, RF field AM modulated 10 V/m 80% AM (1 kHz), 80 – 800 MHz
20 V/m 80% AM (1 kHz), 800 – 1000 MHz
20 V/m 80% AM (1 kHz), 1400 – 2700 MHz
ENV 50204, RF field 900 MHz Enclosure, 20 V/m pulse modulated 200 Hz, 900 ± 5 MHz
EN 61000-4-4, fast transients Signal ports, ± 2 kV
Power ports, ± 2 kV
EN 61000-4-5, surge Signal ports unbalanced, ± 2 kV line to earth, ± 2 kV line to line
Signal ports balanced, ± 2 kV line to earth, ± 1 kV line to line
Power ports, ± 2 kV line to earth, ± 2 kV line to line
EN 61000-4-6, conducted RF immunity Signal ports, 10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports, 10 V 80% AM (1 kHz), 0.15 – 80 MHz
EN 61000-4-9, pulsed magnetic field Enclosure, 300 A/m, 6.4 / 16 μs pulse
EN 61000-4-11, Voltage dips and interruption AC power ports, 10 & 5 000 ms, interruption, 200 ms, 40% residual voltage, 500 ms, 70% residual voltage
EN 61000-4-16, Mains freq. 50 Hz Signal ports, 100 V 50 Hz line to earth
SS 436 15 03, Mains freq. 50 Hz Signal ports, 250 V 50 Hz line to line
EN 55022, radiated RF emission Enclosure, Class B
FCC part 15, radiated RF emission Enclosure, Class A
EN 55022, conducted emission AC power ports, Class B
DC power ports, Class A
FCC part 15, conducted emission AC power ports, Class B
• Safety
Safety UL/CSA/IEC/EN
EN 60950-1,dielectric strength Signal port to all other isolated ports
2 kVrms 50 Hz 1minPower port to other isolated ports
3 kVrms 50 Hz 1min
2 kVrms 50 Hz 1min (@ rated power < 60V)
• Climatic
Temperature, operating –40 to +60°C (–40 to +140°F)
Temperature, storage –40 to +70ºC (–40 to +158ºF)
Humidity, operating 5 to 95% relative humidity
Humidity, storage 5 to 95% relative humidity
• Enclosure
Enclosure UL 94, PC / ABS, Flammability class V-1
Dimensions (W x H x D) 35 x 121 x 119 mm (1.37 x 4.76 x 4.68 in)
Weight 0.26 kg
Degree of protection IP 21
Cooling Convection
Mounting Horizontal on 35 mm DIN-rail
• Mechanical
IEC 60068-2-6, vibration Operating, 7.5 mm, 5 – 8 Hz, 2 g, 8 – 500 Hz
IEC-60068-2-27, shock Operating, 15 g, 11 ms
• Interface specifications, power
Operating voltage 10 to 60 VDC and 20 to 30 VAC
Rated voltage 12 to 48 VDC and 24 VAC
Rated current 300 mA @ 12 VDC
150 mA @ 24 VDC
75 mA @ 48 VDC
Rated frequency DC and 48 to 62 Hz
Inrush current 0.2 A²s
Startup current 1.0 Apeak
Polarity Reverse polarity protected
Redundant power input Yes
Isolation to PROFIBUS DP and Status port
Connection Detachable screw terminal
Connector size 0.75 – 2.5 mm² (AWG 18 – 13). Connect the unit using at least 18 AWG (0.75 mm2) wiring
Shielded cable Not required
• Interface specifications, status
Port type Signal relay, changeover contacts
Rated voltage Up to 48 VDC
Operating voltage Up to 60 VDC
Contact rating 500 mA @ 48 VDC
Contact resistance < 50 m Ohm
Isolation to PROFIBUS DP and Power port
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm² (AWG 24 – 13)
Shielded cable Not required
• Interface specifications, Profibus DP (RS-485)
Electrical specification EIA RS-485 / EN 50 170
Data rate 9 600 bit/s, 19.2, 93.75, 187.5, 500 kbit/s, 1.5, 3, 6 and 12 Mbit/s
Data format 8 data bits, even parity, 1 stop bit, 11 bits total
Protocol PROFIBUS DP / EN 50170
Data rate detection Yes, compliant with EN 50 170
Retiming Yes
Turn around time In accordance with EN 50 170
Transmission range ≤ 1200 m, depending on data rate and cable type (EIA RS-485)
Settings None, external termination and failsafe biasing
Protection Installation Fault Tolerant (up to ±60 V)
Isolation to Power and Status port
Connection 9-pin D-sub female
Shielded cable Not required
Conductive housing Isolated to all other circuits and housings
• Product Description
Status Active
Article number 3651-3712
Ports 1 x Detachable screw terminal, Status
1 x PROFIBUS DP (RS-485)
1 x LC Duplex or LC Simplex, FX (Fibre)
Description Point-to-Point Fibre Converter, PROFIBUS
• Approvals
Hazardous locations ATEX, EN 60079-0 and EN 60079-15
• Reliability prediction
Service life, operating Operating,10 years
• EMC (Electromagnetic Compatibility)
EN 61000-6-1 Immunity residential environments
EN 61000-6-2 Immunity industrial environments
EN 61000-6-3 Emission residential environments
EN 61000-6-4 Emission industrial environments
EN 55022 Emission IT equipment, class A
EN 55024 Immunity IT equipment
FCC part 15 Class A
EN 50121-4 Railway signalling and telecommunications apparatus
IEC 62236-4 Railway signalling and telecommunications apparatus
• EMC Specification
EN 61000-4-2, ESD Enclosure contact, ± 6 kV
Enclosure air, ± 8 kV
IEC 61000-4-3, RF field AM modulated 10 V/m 80% AM (1 kHz), 80 – 800 MHz
20 V/m 80% AM (1 kHz), 800 – 1000 MHz
20 V/m 80% AM (1 kHz), 1400 – 2700 MHz
ENV 50204, RF field 900 MHz Enclosure, 20 V/m pulse modulated 200 Hz, 900 ± 5 MHz
EN 61000-4-4, fast transients Signal ports, ± 2 kV
Power ports, ± 2 kV
EN 61000-4-5, surge Signal ports unbalanced, ± 2 kV line to earth, ± 2 kV line to line
Signal ports balanced, ± 2 kV line to earth, ± 1 kV line to line
Power ports, ± 2 kV line to earth, ± 2 kV line to line
EN 61000-4-6, conducted RF immunity Signal ports, 10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports, 10 V 80% AM (1 kHz), 0.15 – 80 MHz
EN 61000-4-9, pulsed magnetic field Enclosure, 300 A/m, 6.4 / 16 μs pulse
EN 61000-4-11, Voltage dips and interruption AC power ports:
10 & 5 000 ms, interruptio
200 ms, 40% residual voltage
500 ms, 70% residual voltage
EN 61000-4-16, Mains freq. 50 Hz Signal ports, 100 V 50 Hz line to earth
SS 436 15 03, Mains freq. 50 Hz Signal ports, 250 V 50 Hz line to line
EN 55022, radiated RF emission Enclosure, Class B
FCC part 15, radiated RF emission Enclosure, Class A
EN 55022, conducted emission AC power ports, Class B
DC power ports, Class A
FCC part 15, conducted emission AC power ports, Class B
• Safety
Safety EN 60950-1, IT equipment
EN 60950-1,dielectric strength Signal port to all other isolated ports:
2 kVrms 50 Hz 1min
Power port to other isolated ports:
3 kVrms 50 Hz 1min
2 kVrms 50 Hz 1min (@ rated power < 60V)
• Climatic
Temperature, operating –40 to +60°C (–40 to +140°F)
Temperature storage –40 to +70°C (–40 to +158°F)
Maximum surface temperature 135°C (temperature class T4)
Humidity, operating 5 to 95% relative humidity
Humidity, storage 5 to 95% relative humidity
• Enclosure
Enclosure Cabelec 6141
Dimensions (W x H x D) 35 x 121 x 119 mm (1.37 x 4.76 x 4.68 in)
Weight 0.26 kg
Degree of protection IP 21
Cooling Convection
Mounting Horizontal on 35 mm DIN-rail
• Mechanical
IEC 60068-2-6, vibration Operating, 7.5 mm, 5 – 8 Hz, 2 g, 8 – 500 Hz
IEC-60068-2-27, shock Operating, 15 g, 11 ms
• Interface specifications, power
Operating voltage 10 to 60 VDC
Rated voltage 12 to 48 VDC
Rated current 300 mA @ 12 VDC
150 mA @ 24 VDC
75 mA @ 48 VDC
Rated frequency DC
Inrush current 0.2 A²s
Startup current 1.0 Apeak
Polarity Reverse polarity protected
Redundant power input Yes
Isolation to PROFIBUS DP and Status port
Connection Detachable screw terminal
Connector size 0.75 – 2.5 mm² (AWG 18 – 13). Connect the unit using at least 18 AWG (0.75 mm2) wiring
Shielded cable Not required
• Interface specifications, status
Port type Signal relay, changeover contacts
Rated voltage Up to 48 VDC
Operating voltage Up to 60 VDC
Contact rating 500 mA @ 48 VDC
Contact resistance < 50 m Ohm
Isolation to PROFIBUS DP and Power port
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm² (AWG 24 – 13)
Shielded cable Not required
• Interface specifications, PROFIBUS DP (RS-485)
Electrical specification EIA RS-485 / EN 50 170
Data rate 9 600 bit/s, 19.2, 93.75, 187.5, 500 kbit/s, 1.5, 3, 6 and 12 Mbit/s
Data format 8 data bits, even parity, 1 stop bit, 11 bits total
Protocol PROFIBUS DP / EN 50170
Data rate detection Yes, compliant with EN 50 170
Retiming Yes
Turn around time In accordance with EN 50 170
Transmission range ≤ 1200 m, depending on data rate and cable type (EIA RS-485)
Settings None, external termination and failsafe biasing
Protection Installation Fault Tolerant (up to ±60 V)
Isolation to Power and Status port
Connection 9-pin D-sub female
Shielded cable Not required
Conductive housing Isolated to all other circuits and housings